About Nexans
Products and Solutions
Customer Service
Work at Nexans
News and Press
These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control in moist areas and where aliphatic and aromatic hydrocarbons may be present. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant...). Hypron® offers an alternative to conventional lead sheathed cable and is an environmental friendly solution. They maintain circuit integrity when exposed to fire.
Conductor:
Stranded or flexible bare copper
Insulation:
Mica tape
Cross-linked polyethylene (XLPE)
Binder tape:
Bedding:
Inner sheath:
Low Smoke Zero Halogen (LSZH)
Colour: black.
Overall screen/sealing barrier:
Tinned copper drain wire
Aluminium/polyethylene tape
High density polyethylene (PE)
Colour: black
Special sheath (intermediate sheath):
Polyamide
Armour:
Galvanized steel wires (SWA)
Outer sheath:
Polyvinyl chloride (PVC)
Other colour on request.
Pair: black - white Quad: black - white - red- blue (2 pair cables are assembled as a quad) White core printed with pair number On request according to PAS 5308 part 1
NEXANS 279 MGT/XLPE/AL/HDPE/NC/SWA/PVC 300/500V Nber of pairs & cross-section Cu IEC 60331 IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking
PAS 5308 Part 1/type 2 (Design guide-lines) BS EN 60228-2005
Minimum bending radius:
15 x outer diameter To be doubled during laying operations
Tinned copper conductors available on request