Login Get Registered Catalog Browser Contact Us
Nexans in Qatar

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

EN 50288-7 XLPE Insulation IOS Armoured LC Fire Retardant

Send link to this page print Your Nexans contact on this page
EN 50288-7 XLPE Insulation IOS Armoured LC Fire Retardant - Instrumentation cables 170/300 V
- With lead cover (LC)
- Individual & Overall Screen (IOS)
- Aliphatic and aromatic hydrocarbons resistant
Standards
International  IEC 60332-3-22 Cat.A
Description

Applications

These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control. They are well adapted to underground use in industrial applications, in moist areas, where hydrocarbon and mechanical protection are needed. The lead cover brings an enhanced resistance to aromatics hydrocarbons. The individual screening of each pair limits the consequence of crosstalk

 

Design

Conductor:

Stranded bare copper class 2

Insulation:

Cross-linked polyethylene (XLPE)

Individual screen

Polyester tape

Tinned copper drain wire, 

Aluminium backed polyester tape

Polyester tape

Overall screen

Polyester tape

Tinned copper drain wire, 

Aluminium backed polyester tape

Inner sheath:

Polyvinyl chloride (PVC)

Colour: black

Lead sheath:

Bedding (intermediate sheath):

Polyvinyl chloride (PVC)

Colour: black

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC)

Colour: black

Other colour on request.

 

Core identification

Pair: white - black
White core printed with pair number
 

 

Marking

NEXANS 279 XLPE/IND.+OA.SCR/PVC//LC/PVC/SWA/PVC 170/300V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

EN 50288-7 (Design guide-lines)


 TOP
Characteristics
Construction characteristics
Conductor material Bare copper  
Type of conductor Stranded, Class 2  
Insulation PRC  
Individual screen Tinned copper drain wire + aluminium/polyester tape  
Overall screen Tinned copper drain wire + aluminium/polyester tape  
Inner sheath PVC  
Lead Sheath Yes  
Intermediate sheath PVC  
Armour type Galvanized steel wires  
Outer sheath Tight buffer  
Protection Yes  
Electrical characteristics
Rated Voltage Uo/U (Um) 170/300V  
Mechanical characteristics
Mechanical resistance to impacts Good  
Usage characteristics
Fire retardant IEC 60332-3-22  
Chemical resistance Aliphatic and aromatic hydrocarbons resistant  
Electro magnetic interference resistance Yes  
Operating temperature, range -20 .. 60°C  
Max. conductor temperature in service 90°C  
Standard EN  

 TOP
Your selection
Number of pairs  
Conductor cross-section  mm²
Apply
Reset
Results   25/25
Select all Items Nexans ref. Name nb pairs Cross section (mm²)
Make to order product 10134931 EN 50288-7 XLPE IOS Armoured LC 2x2x0,5 2 0.5
Make to order product 10164888 EN 50288-7 XLPE IOS Armoured LC 5x2x0,5 5 0.5
Make to order product 10186831 EN 50288-7 XLPE IOS Armoured LC 10x2x0,5 10 0.5
Make to order product 10134936 EN 50288-7 XLPE IOS Armoured LC 20x2x0,5 20 0.5
Make to order product EN 50288-7 XLPE IOS Armoured LC 30x2x0,5 30 0.5
Make to order product 10134938 EN 50288-7 XLPE IOS Armoured LC 2x2x0,75 2 0.75
Make to order product 10186837 EN 50288-7 XLPE IOS Armoured LC 5x2x0,75 5 0.75
Make to order product 10164888 EN 50288-7 XLPE IOS Armoured LC 10x2x0,75 10 0.75
Make to order product 10134943 EN 50288-7 XLPE IOS Armoured LC 20x2x0,75 20 0.75
Make to order product EN 50288-7 XLPE IOS Armoured LC 30x2x0,75 30 0.75
Make to order product 10134945 EN 50288-7 XLPE IOS Armoured LC 2x2x1 2 1
Make to order product 10186845 EN 50288-7 XLPE IOS Armoured LC 5x2x1 5 1
Make to order product 10186848 EN 50288-7 XLPE IOS Armoured LC 10x2x1 10 1
Make to order product 10134950 EN 50288-7 XLPE IOS Armoured LC 20x2x1 20 1
Make to order product EN 50288-7 XLPE IOS Armoured LC 30x2x1 30 1
Make to order product 10134952 EN 50288-7 XLPE IOS Armoured LC 2x2x1,5 2 1.5
Make to order product 10186853 EN 50288-7 XLPE IOS Armoured LC 5x2x1,5 5 1.5
Make to order product 10186856 EN 50288-7 XLPE IOS Armoured LC 10x2x1,5 10 1.5
Make to order product 10134957 EN 50288-7 XLPE IOS Armoured LC 20x2x1,5 20 1.5
Make to order product EN 50288-7 XLPE IOS Armoured LC 30x2x1,5 30 1.5
Make to order product 10186861 EN 50288-7 XLPE IOS Armoured LC 2x2x2,5 2 2.5
Make to order product 10186864 EN 50288-7 XLPE IOS Armoured LC 5x2x2,5 5 2.5
Make to order product 10186868 EN 50288-7 XLPE IOS Armoured LC 10x2x2,5 10 2.5
Make to order product 10186874 EN 50288-7 XLPE IOS Armoured LC 20x2x2,5 20 2.5
Make to order product EN 50288-7 XLPE IOS Armoured LC 30x2x2,5 30 2.5
Add to favorites

 TOP
Selling delivery information

Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.


Minimum bending radius:

10 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request


EN 50288-7 XLPE Insulation IOS Armoured LC Fire Retardant   Electrical Charasteristics (30 kB)

Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map