Applications
Airfield Lighting Equipment Primary cable for the serie circuit connecting the Constant Current Regulators and the isolating transformers, and between isolating transformers.
This cable can be directly buried in ground without mechanical protection, but keeping with common practices (sand bedding, warning grid...)
Design
- Conductor
Stranded bare copper (RM), Class 2, IEC 60228
- Insulation
Extruded triple dielectric of internal semi-conductor natural colored cross-linked Polyethylene XLPE insulation and external semi-conductor (strippable)
- Screen
Concentric layer of bare copper wire, counter helix of a copper tape
- Outer sheath
PVC (polyvinyl chloride)
Colour : red
Marking
NEXANS 205 - FL2XCY 1 x 6 RM/6
type 7kV - ENV 50213 - week - year
Minimum bending radius
During installation (dynamic) : 20 x D
After installation (static) : 10 x D
Volatge test between conductor and metallic screen
15 kV - 50Hz - 5 min
7kV primary circuit cables are in accordance with IEC 60502-2 requirements stated for 6/10(12)kV cables
|