Application
Airfield Lighting Equipment Primary cables for serie circuit connecting the Constant Current Regulators and the isolating transformers, and between isolating transformers.
This cable can be directly buried in ground without mechanical protection, but keeping with common practices (sand bedding, warning grid ...).
Design
Conductor
- Stranded Bare
- Class 2
- Cross section: 6 mm² or 8 AWG (8.37 mm²)
- IEC 60 228 ( for 6 mm²)
Semi conductor
Insulation
- XLPE (cross linked polyethylene)
Screen
Outer sheath
- PE (polyethylene), or PVC (polyvinyl chloride), or XLPE (cross linked polyethylene)
Marking
NEXANS 205 - FAA L-824 C 1 x 6 mm² - 5 kV - week - year
Minimum bending radius
- During installation (dynamic): 20 x D
- After installation (static): 10 x D
Volatge test between conductor and water
|