PAS 5308 Part 1/Type 1 IOS Fire retardant

Send link to this page print Your Nexans contact on this page
PAS 5308 Part 1/Type 1 IOS Fire retardant - Instrumentation cables 300/500 V
- XLPE insulation (Part 1)
- Unarmoured (Type 1)
- Individual & Overall Screen (IOS)
- Oil resistant
Standards
International  IEC 60332-3-22 Cat.A
National  BS 5308; BS 6234; BS 6360; BS 6746
Description

Applications

These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control where chemicals may be present. The individual screening of each pair limits the consequence of crosstalk..

 

Design

Conductor:

Solid, stranded or flexible bare copper

Insulation:

Cross-linked polyethylene (XLPE)

Individual screen

Binder tape

Tinned copper drain wire, 

Aluminium/polyester tape

Binder tape

Overall screen

Binder tape

Tinned copper drain wire, 

Aluminium/polyester tape

Outer sheath:

Polyvinyl chloride (PVC)

Colour: black

Other colour on request.

 

Core identification

Pair: black - white
White core printed with pair number
On request: according to PAS 5308 part 1

 

Marking

NEXANS 279 XLPE/IND.+OA.SCR/PVC 300/500V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

PAS 5308 Part 1/type 1 (Design guide-lines)
BS EN 60228-2005
BS EN 50290-2-29



Related documents
  Electrical-characteristics-PAS_5308_Part_1  (37.0kb)



 TOP
Characteristics
Construction characteristics
Conductor material Bare copper  
Insulation XLPE (Cross-linked Polyethylene)  
Individual screen Tinned copper drain wire + aluminium/polyester tape  
Overall screen Tinned copper drain wire + aluminium/polyester tape  
Outer sheath PVC  
Protection no  
Electrical characteristics
Rated Voltage Uo/U (Um) 300 / 500 V  
Usage characteristics
Fire retardant IEC 60332-3-22  
Oil resistance Yes  
Electro magnetic interference resistance Yes  
Operating temperature, range -20 .. 60°C  
Max. conductor temperature in service 90°C  
Standard PAS  

 TOP
Selling delivery information

Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.


Minimum bending radius:

10 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request