Login Get Registered Catalog Browser Contact Us
Nexans in Qatar

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

PAS 5308 Part 1/Type 2 OS Fire retardant

Send link to this page print Your Nexans contact on this page
PAS 5308 Part 1/Type 2 OS Fire retardant - Instrumentation cables 300/500 V
- XLPE insulation (Part 1)
- Armoured (Type 2)
- Overall Screen (OS)
- Oil resistant
Standards
International  IEC 60332-3-22 Cat.A
National  BS 5308; BS 6234; BS 6360; BS 6746
Description

Applications

These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control .They are well adapted to  underground use in industrial application where chemical and mechanical protections are needed (refinery areas, chemical plant…) .

 

Design

Conductor:

Solid, stranded or flexible bare copper

Insulation:

Cross-linked polyethylene (XLPE)

Overall screen

Binder tape

Tinned copper drain wire, 

Aluminium/polyester tape

Bedding (inner sheath):

Polyvinyl chloride (PVC).

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC)

Colour: black

Other colour on request.

 

Core identification

Pair: black - white
Quad: black - white - red - blue (2 pair cables assembled as a quad)
White core printed with pair number
On request: according to PAS 5308 part 1

 

Marking

NEXANS 279 XLPE/OA.SCR/PVC/SWA/PVC 300/500V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

PAS 5308 Part 1/type 2 (Design guide-lines)
BS EN 60228-2005
BS EN 50290-2-29



Related documents
  Electrical-characteristics-PAS_5308_Part_1  (37.0kb)



 TOP
Characteristics
Construction characteristics
Conductor material Bare copper  
Insulation XLPE (Cross-linked Polyethylene)  
Overall screen Tinned copper drain wire + aluminium/polyester tape  
Inner sheath PVC  
Armour type Galvanized steel wires  
Outer sheath PVC  
Protection Yes  
Electrical characteristics
Rated Voltage Uo/U (Um) 300 / 500 V  
Mechanical characteristics
Mechanical resistance to impacts Good  
Usage characteristics
Fire retardant IEC 60332-3-22  
Oil resistance Yes  
Electro magnetic interference resistance Yes  
Operating temperature, range -20 .. 60°C  
Max. conductor temperature in service 90°C  
Standard PAS  

 TOP
Your selection
Number of pairs  
Conductor cross-section  mm²
Type of conductor  
Apply
Reset
Results   36/36
Select all Items Nexans ref. Name nb pairs Cross section (mm²) Type of conductor
Make to order product 10112085 PAS 5308 Part1/type 2 OS 10x2x0,5 10 0.5 Circula, Flexible, Class 5
Make to order product 10112078 PAS 5308 Part1/type 2 OS 10x2x0,5 10 0.5 Solid, Class 1
Make to order product 10164987 PAS 5308 Part1/type 2 OS 10x2x0,75 10 0.75 Stranded, Class 2
Make to order product 10112092 PAS 5308 Part1/type 2 OS 10x2x1 10 1 Solid, Class 1
Make to order product 10112099 PAS 5308 Part1/type 2 OS 10x2x1,5 10 1.5 Stranded, Class 2
10164994 PAS 5308 Part1/type 2 OS 10x2x2,5 10 2.5 Stranded, Class 2
Make to order product 10112075 PAS 5308 Part1/type 2 OS 1x2x0,5 1 0.5 Solid, Class 1
Make to order product 10112082 PAS 5308 Part1/type 2 OS 1x2x0,5 1 0.5 Circula, Flexible, Class 5
Make to order product 10164984 PAS 5308 Part1/type 2 OS 1x2x0,75 1 0.75 Stranded, Class 2
Make to order product 10112089 PAS 5308 Part1/type 2 OS 1x2x1 1 1 Solid, Class 1
Make to order product 10112096 PAS 5308 Part1/type 2 OS 1x2x1,5 1 1.5 Stranded, Class 2
10164991 PAS 5308 Part1/type 2 OS 1x2x2,5 1 2.5 Stranded, Class 2
Make to order product 10112079 PAS 5308 Part1/type 2 OS 20x2x0,5 20 0.5 Solid, Class 1
Make to order product 10112086 PAS 5308 Part1/type 2 OS 20x2x0,5 20 0.5 Circula, Flexible, Class 5
Make to order product 10164988 PAS 5308 Part1/type 2 OS 20x2x0,75 20 0.75 Stranded, Class 2
Make to order product 10112093 PAS 5308 Part1/type 2 OS 20x2x1 20 1 Solid, Class 1
10112100 PAS 5308 Part1/type 2 OS 20x2x1,5 20 1.5 Stranded, Class 2
10164995 PAS 5308 Part1/type 2 OS 20x2x2,5 20 2.5 Stranded, Class 2
Make to order product 10112076 PAS 5308 Part1/type 2 OS 2x2x0,5 2 0.5 Solid, Class 1
Make to order product 10112083 PAS 5308 Part1/type 2 OS 2x2x0,5 2 0.5 Circula, Flexible, Class 5
Make to order product 10164985 PAS 5308 Part1/type 2 OS 2x2x0,75 2 0.75 Stranded, Class 2
Make to order product 10112090 PAS 5308 Part1/type 2 OS 2x2x1 2 1 Solid, Class 1
Make to order product 10112097 PAS 5308 Part1/type 2 OS 2x2x1,5 2 1.5 Stranded, Class 2
10164992 PAS 5308 Part1/type 2 OS 2x2x2,5 2 2.5 Stranded, Class 2
Make to order product 10112080 PAS 5308 Part1/type 2 OS 30x2x0,5 30 0.5 Solid, Class 1
Make to order product 10112087 PAS 5308 Part1/type 2 OS 30x2x0,5 30 0.5 Circula, Flexible, Class 5
Make to order product 10164989 PAS 5308 Part1/type 2 OS 30x2x0,75 30 0.75 Stranded, Class 2
Make to order product 10112094 PAS 5308 Part1/type 2 OS 30x2x1 30 1 Solid, Class 1
10112101 PAS 5308 Part1/type 2 OS 30x2x1,5 30 1.5 Stranded, Class 2
10166442 PAS 5308 Part1/type 2 OS 30x2x2,5 30 2.5 Stranded, Class 2
Make to order product 10112084 PAS 5308 Part1/type 2 OS 5x2x0,5 5 0.5 Circula, Flexible, Class 5
Make to order product 10112077 PAS 5308 Part1/type 2 OS 5x2x0,5 5 0.5 Solid, Class 1
Make to order product 10164986 PAS 5308 Part1/type 2 OS 5x2x0,75 5 0.75 Stranded, Class 2
Make to order product 10112091 PAS 5308 Part1/type 2 OS 5x2x1 5 1 Solid, Class 1
Make to order product 10112098 PAS 5308 Part1/type 2 OS 5x2x1,5 5 1.5 Stranded, Class 2
10164993 PAS 5308 Part1/type 2 OS 5x2x2,5 5 2.5 Stranded, Class 2
Add to favorites

 TOP
Selling delivery information

Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.


Minimum bending radius:

10 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request


PAS 5308 Part 1/Type 2 OS Fire retardant   Electrical-characteristics-PAS_5308_Part_1 (37 kB)

Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map