About Nexans
Products and Solutions
Customer Service
Work at Nexans
News and Press
These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control. They are well adapted to underground use in industrial applications, in moist areas, where hydrocarbon and mechanical protection are needed. The lead cover brings an enhanced resistance to aromatics hydrocarbons.
Conductor:
Solid, stranded or flexible bare copper
Insulation:
Cross-linked polyethylene (XLPE)
Overall screen:
Binder tape
Tinned copper drain wire,
Aluminium/polyester tape
Bedding (inner sheath):
Polyvinyl chloride (PVC)
Colour: black
Lead covering:
Lead alloy "E"
Bedding (intermediate sheath):
Armour:
Galvanized steel wires (SWA)
Outer sheath:
Other colour on request.
Pair: black - white Quad: black - white - red - blue (2 pair cables assembled as a quad) White core printed with pair number On request: according to PAS 5308 part 1
NEXANS 279 XLPE/OA.SCR/PVC//LC/PVC/SWA/PVC 300/500V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking
PAS 5308 Part 1/type 3 (Design guide-lines) BS EN 60228-2005 BS EN 50290-2-29
Minimum bending radius:
10 x outer diameter To be doubled during laying operations
Tinned copper conductors available on request