PAS 5308 Part 2/Type 2 OS Fire retardant

Send link to this page print Your Nexans contact on this page
PAS 5308 Part 2/Type 2 OS Fire retardant - Instrumentation cables 300/500 V
- PVC insulation (Part 2)
- Armoured (Type 2)
- Overall Screen (OS)
- Oil resistant
Standards
International  IEC 60332-3-22 Cat.A
National  BS 1442; BS 5308; BS 6360; BS 6746
Description

Applications

These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control .They are well adapted to underground use in industrial application where chemical and mechanical protections are needed (refinery areas, chemical plant…) .

 

Design

Conductor:

Stranded or flexible bare copper

Insulation:

Polyvinyl chloride (PVC)

Overall screen

Binder tape

Tinned copper drain wire, 

Aluminium/polyester tape

Bedding (inner sheath):

Polyvinyl chloride (PVC).

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC)

Colour: black

Other colour on request.

 

Core identification

Pair: black - white
Quad: black - white - red - blue (2 pair cables assembled as a quad)
White core printed with pair number
On request: according to PAS 5308 part 2

 

Marking

NEXANS 279 PVC/OA.SCR/PVC/SWA/PVC 300/500V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

PAS 5308 Part 2/type 2 (Design guide-lines)
BS EN 60228-2005
BS EN 50290-2-21-2002



Related documents
  Electrical characteristics Pas 5308 Part 2  (28.3kb)



 TOP
Characteristics
Construction characteristics
Conductor material Bare copper  
Insulation PVC  
Overall screen Tinned copper drain wire + aluminium/polyester tape  
Inner sheath PVC  
Armour type Galvanized steel wires  
Outer sheath PVC  
Protection Yes  
Electrical characteristics
Rated Voltage Uo/U (Um) 300 / 500 V  
Mechanical characteristics
Mechanical resistance to impacts Good  
Usage characteristics
Fire retardant IEC 60332-3-22  
Oil resistance Yes  
Electro magnetic interference resistance Yes  
Operating temperature, range -20 .. 60°C  
Max. conductor temperature in service 70°C  
Standard PAS  

 TOP
Your selection
Number of pairs  
Conductor cross-section  mm²
Type of conductor  
Apply
Reset
Results   30/30
Select all Items Nexans ref. Name nb pairs Cross section (mm²) Type of conductor
Make to order product 10112221 PAS 5308 Part 2/type 2 OS 10x2x0,5 10 0.5 Circula, Flexible, Class 5
Make to order product 10112228 PAS 5308 Part 2/type 2 OS 10x2x0,75 10 0.75 Circula, Flexible, Class 5
Make to order product PAS 5308 Part 2/type 2 OS 10x2x1 10 1 Stranded, Class 2
10112235 PAS 5308 Part 2/type 2 OS 10x2x1,5 10 1.5 Stranded, Class 2
PAS 5308 Part 2/type 2 OS 10x2x2,5 10 2.5 Stranded, Class 2
Make to order product 10112218 PAS 5308 Part 2/type 2 OS 1x2x0,5 1 0.5 Circula, Flexible, Class 5
Make to order product 10112225 PAS 5308 Part 2/type 2 OS 1x2x0,75 1 0.75 Circula, Flexible, Class 5
Make to order product PAS 5308 Part 2/type 2 OS 1x2x1 1 1 Stranded, Class 2
Make to order product 10112232 PAS 5308 Part 2/type 2 OS 1x2x1,5 1 1.5 Stranded, Class 2
10167035 PAS 5308 Part 2/type 2 OS 1x2x2,5 1 2.5 Stranded, Class 2
Make to order product 10112222 PAS 5308 Part 2/type 2 OS 20x2x0,5 20 0.5 Circula, Flexible, Class 5
Make to order product 10112229 PAS 5308 Part 2/type 2 OS 20x2x0,75 20 0.75 Circula, Flexible, Class 5
Make to order product PAS 5308 Part 2/type 2 OS 20x2x1 20 1 Stranded, Class 2
10112236 PAS 5308 Part 2/type 2 OS 20x2x1,5 20 1.5 Stranded, Class 2
PAS 5308 Part 2/type 2 OS 20x2x2,5 20 2.5 Stranded, Class 2
Make to order product 10112219 PAS 5308 Part 2/type 2 OS 2x2x0,5 2 0.5 Circula, Flexible, Class 5
Make to order product 10112226 PAS 5308 Part 2/type 2 OS 2x2x0,75 2 0.75 Circula, Flexible, Class 5
Make to order product PAS 5308 Part 2/type 2 OS 2x2x1 2 1 Stranded, Class 2
Make to order product 10112233 PAS 5308 Part 2/type 2 OS 2x2x1,5 2 1.5 Stranded, Class 2
PAS 5308 Part 2/type 2 OS 2x2x2,5 2 2.5 Stranded, Class 2
Make to order product 10112223 PAS 5308 Part 2/type 2 OS 30x2x0,5 30 0.5 Circula, Flexible, Class 5
Make to order product 10112230 PAS 5308 Part 2/type 2 OS 30x2x0,75 30 0.75 Circula, Flexible, Class 5
Make to order product PAS 5308 Part 2/type 2 OS 30x2x1 30 1 Stranded, Class 2
10112237 PAS 5308 Part 2/type 2 OS 30x2x1,5 30 1.5 Stranded, Class 2
PAS 5308 Part 2/type 2 OS 30x2x2,5 30 2.5 Stranded, Class 2
Make to order product 10112220 PAS 5308 Part 2/type 2 OS 5x2x0,5 5 0.5 Circula, Flexible, Class 5
Make to order product 10112227 PAS 5308 Part 2/type 2 OS 5x2x0,75 5 0.75 Circula, Flexible, Class 5
Make to order product PAS 5308 Part 2/type 2 OS 5x2x1 5 1 Stranded, Class 2
Make to order product 10112234 PAS 5308 Part 2/type 2 OS 5x2x1,5 5 1.5 Stranded, Class 2
PAS 5308 Part 2/type 2 OS 5x2x2,5 5 2.5 Stranded, Class 2
Add to favorites

 TOP
Selling delivery information

Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.


Minimum bending radius:

10 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request