U-1000 R2V cables can be used in all low voltage power installations. Multiconductors cables are adapted to remote control and telecontrol installations.
In case of high ambiant temperature, use correction coefficient.
These cables can be fixed on cable trays, within conduits or fixed to walls. They also can be buried directly with extra mechanical protection.
Cross sections 1,5 - 2,5 and 4 mm² have to be of class 2 flexiblility, if the cable is connected to equipment subject to vibration.
n (x or G) s mm² U-1000 R2V NF - USE N° Plant S.Y +
Permissible current and voltage drop are given
For 1 conductor , 4 and 5 conductors and 3 conductors without ground (1x, 3x, 4x,4G, 5x, 5G) according to a THREE PHASE CURRENT a) in free air, sheltered from sun, on cable tray or bracket, on cable ladder, and spaced from the wall, temperature = 30°C. b) buried with thermal resistivity of the ground 1Km/W, laying depth : 600 mm, temperature = 20°C.
If conditions are differents, apply correction factors from NF C 15-100 standard or equivalent national standard
For 2 and 3 conductors with ground (2x and 3G); according to a SINGLE PHASE CURRENT = a) in free air, sheltered from sun, on cable tray or bracket, on cable ladder, and spaced from the wall, temperature = 30°C. b) buried with thermal resistivity of the ground 1Km/W, laying depth : 600 mm, temperature = 20°C.
If conditions are differents, apply correction factors from NF C 15-100 standard
Voltage drop
Calculated with cosj = 0,8
Number of cores
HD 308 S2 since january 2004
G (earth core)
X (without earth core)
1
Black (preferential)
2
Blue + Brown
3*
Green - Yellow + Blue + Brown
Brown + Black + Grey
3**
Blue + Brown + Black
4
Green - Yellow + Brown + Black + Grey
Blue + Brown + Black + Grey
5
Green - Yellow + Blue + Brown + Black + Grey
Blue + Brown + Black + Grey + Black
> 5
White printed numbers + 1 Green - Yellow
White printed numbers
* For the cables without Green/Yellow with a cross-section >4mm²
** For the cables without Green/Yellow with a cross-section of 1,5mm² & 2,5mm²