Application
ALSECURE® cables are designed to be used in private residences or public areas, in all premises open to the public, in transport infrastructures (tunnels, airports, subways ...) and industries, for power circuits.
ALSECURE® cables are fire retardant, low smoke and halogen free. In the event of fire, emitted gases are non corrosive and have a very low toxicity.
Installation
ALSECURE® cables will be installed in accordance with the current regulation.
In case of laying operation between 0°C and -10°C, warm up the cables in a heated room 48 hours minimum before installation.
ALSECURE® cables are not designed for buried installation.
Fire performance
- Fire retardant: IEC 60332-3-24, NF C 32070 Cat. C1, NF EN 50266-2-4
- Flame retardant: IEC 60332-1, NF C 32070 Cat.C2, NF EN 50266-1
- Low smoke: IEC 61034, NF EN 50268-2
- Halogen free: IEC 60754-1, NF EN 50267-2-1
- Low corrosivity: IEC 60754-2, NF EN 50267-2-2
- Low toxicity
- Higher Heating Value: NF EN ISO 1716
Description
Conductor
Bare copper
Stranded class 2
Insulation
XLPE (cross-linked polyethylene)
Outer sheath
Halogen free polyolefin
Colour: green
Marking
ALSECURE FR N1 X1G1-R "nx(or G)S" mm2 0.6/1kV NF-USE 205 week year + metric marking
n: number of cores
S: cross-section (mm²)
"NF-USE" marking is not applicable for cables that are not described in NF C 32-323.
Core identification
(In accordance with european harmonization HD308 S2)
1x: black
2x: brown - blue
3x: brown - black - grey
(brown - black - blue if conductors cross-section is 1.5 or 2.5mm²)
3G: brown - blue - green/yellow
4x: brown - black - grey - blue
4G: brown - black - grey - green/yellow
5x: black cores with printed numbers
5G: blue - brown - black - grey - green/yellow
7 cores and above : black cores with printed numbers
|