Login Get Registered Catalog Browser Contact Us
Nexans in Qatar

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

0.6/1kV BFOU 2C+E,3C+E,4C+E [P5], [P5/P12]

New
Send link to this page print Your Nexans contact on this page
0.6/1kV BFOU 2C+E,3C+E,4C+E [P5], [P5/P12]
  • Power circuit below 1kV, Fire fighting circuit and safety systems.
  • Fixed installation power, control & lighting in both explosion and safe areas, emergency and critical systems.
  • Maximum operating conductor temperature 90°C
Kukdong
Standards
International  IEC 60092-351; IEC 60092-353; IEC 60092-359; IEC 60331; IEC 60332-3 Cat.A; IEC 60754-1; IEC 61034; IEC 61034-2
National  NEK 606; NEK 606
Description

Construction Details
  - Conductor : Circular tinned stranded copper as per IEC 60228, Class 2
  - Fire proof layer : Mica/Glass tape
  - Insulation : Halogen Free Ethylene Propylene Rubber
  - Cabling (with filler)
  - Inner covering : Halogen free thermosetting compound
  - Armour : Copper wire braid
  - Outer sheath :  Halogen-free thermosetting compound, SHF2 or SHF Mud

Earth conductor 
  - 50% of current-carrying phase conductor

Standard Applied
  - Design guideline : NEK 606-2009 & IEC 60092-353
  - Material
    Insulation : HF-EPR as per IEC 60092-351
    Sheath : SHF2 as per IEC 60092-359
  - Flame retardant : IEC 60332-3-22, Cat.A
  - Fire resistant : IEC 60331(-21/-31/-1/-2), 830°C for 120 Min.
 
- Halogen free properties : IEC 60754-1,2
  - Low smoke properties : IEC 61034-1,2
  - Mud resistant : NEK 606-2009
  - Cold properties : CSA C22.2 
  - Sunlight resistance : UL 1581
 
Identification of color
  - Insulation
    3G : Grey, Black, Green/Yellow stripe
    4G : Grey, Black, Red, Green/Yellow stripe
    5G : Grey, Black, Red, Blue, Green/Yellow stripe
    Note) Any other colors is applicable in accordance with
          the CENELEC Harmonization Document HD 308 S2

  - Outer sheath : Black
    Note) Any other colors purchaser required
 
Type approval 
  - ABS, BV, DNV, LR


 TOP
Characteristics
Dimensional characteristics
Number of ground conductors 1.0  
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/ 1 (1.2) kV  

 TOP
Your selection
Number of cores  
Conductor cross-section  mm²
Average insulation thickness  mm
Inner sheath thickness  mm
Diameter over inner sheath  mm
Diameter of wire braids  mm
Diameter over armour  mm
Average sheath thickness  mm
Nominal outer diameter  mm
Approximate weight  kg/km
Apply
Reset
Results   24/24
Select all Items Nexans ref. Name Nb. of cores Cross section (mm²) Av. insul. thickness (mm) Inner sheath thick. (mm) Diam. over inner sheath (mm) Diameter of wire braids (mm) Diam. over armour (mm) Average sheath thickness (mm) Nom. outer diam. (mm) Approx. weight (kg/km)
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 2 25 1.2 1.0 22 0.3 23.6 1.7 27.2 1620
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 2 35 1.2 1.0 24.7 0.3 26.3 1.9 30.3 2105
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 2 50 1.4 1.2 28.5 0.3 30.1 2.0 34.3 2630
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 2 70 1.4 1.2 32.4 0.4 34.4 2.2 39.0 3540
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 2 95 1.6 1.4 37.5 0.4 39.5 2.4 44.5 4670
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 2 120 1.6 1.4 41 0.4 43.0 2.5 48.2 5705
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 2 150 1.8 1.4 45.3 0.4 47.3 2.7 52.9 7000
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 2 185 2.0 1.6 50.1 0.4 52.1 2.9 58.1 8310
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 3 25 1.2 1.0 23.8 0.3 25.4 1.8 29.2 1945
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 3 35 1.2 1.2 27.4 0.3 29.0 2.0 33.2 2600
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 3 50 1.4 1.2 30.7 0.4 32.7 2.1 37.1 3270
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 3 70 1.4 1.2 34.9 0.4 36.9 2.3 41.7 4310
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 3 95 1.6 1.4 40.4 0.4 42.4 2.5 47.6 5715
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 3 120 1.6 1.4 44.4 0.4 46.4 2.7 52.0 7050
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 3 150 1.8 1.6 49.8 0.4 51.8 2.9 57.8 8755
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 3 185 2.0 1.6 54 0.4 56.0 3.0 62.2 10255
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 4 25 1.2 1.2 27.2 0.3 28.8 2.0 33.0 2515
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 4 35 1.2 1.2 30.7 0.4 32.7 2.1 37.1 3355
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 4 50 1.4 1.2 34.5 0.4 36.5 2.3 41.3 4175
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 4 70 1.4 1.4 39.6 0.4 41.6 2.5 46.8 5570
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 4 95 1.6 1.4 45.5 0.4 47.5 2.7 53.1 7350
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 4 120 1.6 1.6 50.4 0.4 52.4 2.9 58.4 9115
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 4 150 1.8 1.6 56 0.4 58.0 3.1 64.4 11205
Make to order product   New 0.6/1kV BFOU [P5], [P5/P12] 4 185 2.0 1.6 61 0.4 63.0 3.3 69.8 13300
Add to favorites

 TOP