Application
ALSECURE® PLUS A Multicores cables are designed to be used in safety systems (emergency lights, warning systems, fire fighting equipments, etc ...) in all premises open to the public (concert hall, theaters, cinemas, department stores, hospitals, schools, etc ...), in high-rises buildings, in tunnels, in industries.
ALSECURE® PLUS A Multicores cables are fire resistant and fire retardant, low smoke and halogen free: in the event of fire, emitted gazes are non corrosive and have a very low toxicity.
Installation
ALSECURE® PLUS A multicores cables will be installed to the wiring regulation and installation standards in force.
Laying temperature : in case of laying between 0°C and -10°C, warm up the cables in a heated room 48 hours minimum before installation.
ALSECURE® PLUS A multicores cables are not designed for buried installation.
Fire performance
- Fire resistant according to IEC 60331, NF C 32-070 Cat. CR1, EN 50200
- Fire retardant according to IEC 60332 Part 2 & 1, NF C 32-070 Cat. C1 & C2, EN 50266
- Low smoke : IEC 61034, NF C 32-073, EN 50268
- Halogen free : IEC 60754, NF C 32-074, EN 50267
- Low toxicity : IEC 60754, NF C 32-074, EN 50267
- Low corrosivity : IEC 60754, NF C 32-074, EN 50267
Marking
ALSECURE PLUS A n (G or x) S mm2 300/500V NF C 32-310 CR1/C1 NF-USE 205
- n = number of cores
- G = with Green/Yellow
- x = without Green/Yellow
- S = section in mm²
|