H07RN-F LINEAX (industrial flexible)

Send link to this page print Your Nexans contact on this page
H07RN-F LINEAX (industrial flexible) Industrial flexible cable, insulation and outer sheath in elastomer
Standards
International  HD 22.4; HD 516; IEC 60245-4 type 66
National  NF C 32-102-4
Description

Application

LINEAX flexible cable is intended for installations with moving equipment, electric appliances and for building sites. The cable may be rated 0,6/1 kV where the installation has built-in protection and for motors in lifting appliances - machine tools - etc.

This cable can be used in refrigerating installations.

 

Installation

This cable can be installed in open air or be buried but with extra mechanical protection.

Conductors laid up 

Assembled conductors.

Marking

USE <'har>N (x ou G) S LINEAX

  • N = number of cores
  • G = with Green-Yellow
  • x = without Green-Yellow
  • S = section in mm²

Nota

Max continuous operating conductor temperature in normal use :

+60°C   ( in every case of mobile installation)

+85°C   ( fixed protected installation )

+200°C ( in short circuit )

 

Permissible current rating is measured for an ambient temperature of 30°C and a maximum operating and conductor temperature of 85°C . For other temperature please refer to correction factors .


 TOP
Characteristics
Construction characteristics
Outer sheath Special cross-linked elastomer  
Sheath colour Black  
Insulation Special cross-linked elastomer  
Conductor material Bare copper  
Electrical characteristics
Rated Voltage Uo/U (Um) 450 / 750 V  
Mechanical characteristics
Mechanical resistance to impacts Very good  
Cable flexibility Flexible  
Usage characteristics
Chemical resistance Accidental  
Water proof Good  
Short-circuit max. conductor temperature 200°C  
Max. conductor temperature in service 60°C  
Operating temperature, range -25 .. 55°C  
Oil resistance Yes  

 TOP
New cores identification
Core identification in accordance with HD 308 S2 (October 2001)Identification of cores in cables and flexible cords.

 

Number of cores

HD 308 S2 since january 2004

G (earth core)

X (without earth core)

1

Black (preferential)

Black (preferential)

2

Blue + Brown

Blue + Brown

3*

Green - Yellow + Blue + Brown 

Brown + Black + Grey

3**

 

Blue + Brown + Black

4

Green - Yellow + Brown + Black + Grey

Blue + Brown + Black + Grey

5

Green - Yellow + Blue + Brown + Black + Grey

Blue + Brown + Black + Grey + Black

>  5

White printed numbers + 1 Green - Yellow

White printed numbers

* For the cables without Green/Yellow with a cross-section >4mm²

** For the cables without Green/Yellow with a cross-section of 1,5mm² & 2,5mm²


 TOP
H07RN-F LINEAX (industrial flexible)   Homologation certificate (317 kB)